Contact Us

Use the form on the right to contact us.

You can edit the text in this area, and change where the contact form on the right submits to, by entering edit mode using the modes on the bottom right. 

3799 Main St. #87024
Atlanta, GA 30337
USA

773.398.5288

Advanced residential construction and home improvement consulting and owner's advocacy in Atlanta, using the latest building performance diagnostic and modeling techniques and tools. Airtightness, insulation, HVAC, ventilation, moisture, and air quality and EMF consulting for homeowners and building professionals alike.

Videos/Podcasts/Articles

Home performance articles and stories from the field with internationally respected building forensics guru Corbett Lunsford at the Building Performance Workshop. Hear new episodes of the Building Performance Podcast, see new videos from the Home Performance YouTube channel, and learn all about how diagnostic testing (more than an 'Energy Audit') can make home improvement and new home construction a proven process!

Filtering by Tag: air leakage

Using Infrared to Find Holes in Your House

Corbett Lunsford

Corbett Lunsford loves infrared cameras (he has six of them, including this FLIR One Pro) but they're not the whole story. Pair your diagnostic tools to be a mastermind of home performance.

Learn more at http://HomePerformance.training

TOOL REVIEW: DG-1000 from Energy Conservatory and Minneapolis Blower Door

Corbett Lunsford

Corbett gives a crash course in the TEC’s DG-1000 used with Minneapolis Blower Door equipment (including the Duct Blaster, TruFlow Plate, and Exhaust Fan Flow Meter). TEC took away a few features like Equivalent Leakage Area estimation, but added the Tubing Assistant and firmware updating, which could endlessly add features based on user feedback.

DEAR CORBETT: Multifamily Blower Door Testing Nuances

Corbett Lunsford

Good day Corbett,

I wanted to let you know, that I really enjoy your approach to the whole building science and your building performance workshop website. I am relatively new as a Resnet Rater and the county where I live is Collier County in Florida.

They recently adopted the new code standard set by the state. My question relates to multifamily condo units. I have a client that did renovations to a 2,500 sq. ft. penthouse condo and the front door to the unit is I a common area. The county wants them to perform a blower door test in order to obtain their certificate of occupancy.

I realize this would be a compartmentalize test, since I can only have access to the unit they renovated for their client. Knowing that I will encounter not only leakage to outside but also internal leakage between units. I was wondering what the best approach would be to ensure a successful test. Collier County requires between 3 ach and 7 ach for a test to pass code.

Any information would be appreciated. Thanking you in advance.

Best Regards,
Norm Giguere
www.blowerdoorenergyexperts.com


Dear Norm-

Thanks for your question, it's a good one! First off, you should be fine if they did a good job with the renovations- 7 ACH50 is not terribly hard to achieve.

When you set up your blower door at the front door of the condo, you'll blow air out into the common hallway, so you want to make sure all possible windows/doors in that hallway are open to the outdoors. Use the emergency exits if necessary (make sure maintenance knows what you're up to).

You'll be testing the condo's leakage to everything outside of it, including the downstairs unit, but that's intended. They really will have air leaking between the two condos, if there are leakage pathways, and you want to be testing for that and including it in your blower door test result.

Ask your code official if they want the result to pass the residential code or commercial code, because you have to test at 75 Pa in commercial. I always advise doing a multipoint test (get the flows on at least two pressures, like 25 Pa and 50 Pa) so you can extrapolate the 75 Pa if anyone ever wants it in the future. Saves you a trip.

AS AN ADDED BONUS, consider doing a Zonal Pressure Test on the unit downstairs, to see how much the blower door is affecting it. Always nice to have more data than you need.

Happy Testing,
Corbett

Tiny House Blower Door Test: #TinyLab Test Series #1

Corbett Lunsford

Watch as Corbett and Grace test their airsealing work on the Tiny Lab with a Retrotec blower door! They fire up the new Model 5000 fan and find that the house has approximately 160 CFM@50 of air leakage, which is 4.7 ACH50 and 0.14 CFM per sq. ft. of enclosure surface area- and that's with stupid tarps over the window holes! We're going to test again when the windows are in.

Thanks to Julie Tolliver of Energy Fitness for Homes for the idea, to Retrotec for making awesome equipment, to 475 High Performance Building Supply for supplying America with awesome airsealing kits, and to Hewlett-Packard for creating awesome video editing stations that we work on every day.